CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers

Note: Change in hours of service.

  • Recalled MA-200-series actuators attached on fire and smoke dampers. Note: Mounting arrangements vary.
Name of Product:
Siebe actuators
Hazard:

he recalled actuators can jam, and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Remedy:
Replace
Recall Date:
June 10, 2009
Units:

Up to 560,000

Consumer Contact

Contact Invensys' Program Coordination Office at (877) 481-2372 between 8 a.m. and 4:30 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at www.regcen.com/MA200.

Recall Details

Description:

WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Invensys Building Systems, of Love Park, Ill., is recalling up to 560,000 Siebe actuators for testing and replacement, if necessary, which could be found in fire and smoke dampers. Actuators hold open fire and smoke dampers in a building's heating, ventilation and air conditioning (HVAC) system. A spring mechanism, integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam, and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing. The actuators have been identified as IBS or Siebe MA 200 and MA-200-1 series with one of the following model numbers: models MA-220, MA-220-0-1, MA-220-0-2, MA-221, MA-221-0-1, MA-221-0-2, MA-223, MA-223-0-1, MA-223-0-2, MA-230, MA 230-0-1, MA-233, MA-233-0-1, MA-240, MA-240-0-1, MA-240-701, MA-240-701-1, MA-243, MA-243-0-1, MA-243-701, MAH-241-0-1, MAH-241-701, and MAH-241-701-1. The Actuators have manufacture date codes of 9348 through 9947. The Actuators were manufactured in the United States.

The MA 200 series Actuators were used in fire/smoke dampers manufactured by the following companies between December 1993 and October 1999: 

CompanyLocation
Accurate Specialty Metal
Arlan Damper Corp
ASL (Tomkins) Limited (Air Systems, Ltd.)
ASL (Tomkins) Limited (Air Systems, Ltd.)
Cesco Products
Greenheck Fan Corp.
Leader Industries
Metalpress Export Ltd.
Nailor Industries
NCA Manufacturing Limited Canada
NCA Manufacturing
Pacific Air Balance, Inc.
P.C.I. (Pottorff).
Prefco Products
Reed National Air Products Group
Ruskin Manufacturing
Brooklyn, NY
Bohemia, NY
New Westminster, BC, Canada
Brampton, ON, Canada
Minneapolis, MN
Schofield, WI
Nashville, TN
Bat Yam, Israel
Houston, TX
Missaugua, ON Canada
Garland, TX
San Fernando, CA
Montebello, CA
Buckingham, PA
Holland, OH
Grandview, MO

Building owners and managers whose buildings have dampers containing Invensys/Siebe actuators should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 8 a.m. and 4:30 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at www.regcen.com/MA200. To be eligible for a free actuator replacement, the building owner must test the actuator per program procedures, and report the results to Invensys' Program Coordination Office on the required forms. Invensys will replace those actuators that fail to properly function during testing.

Building owners with dampers manufactured by Ruskin Manufacturing Co. may have already participated in a similar Replacement Actuator Program conducted by Ruskin. Those building owners also should review this announcement and participate in this recall, as it provides follow-up on Ruskin's program.

Remedy:

Building owners and managers whose buildings have dampers containing Invensys/Siebe actuators should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 8 a.m. and 4:30 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at www.regcen.com/MA200. To be eligible for a free actuator replacement, the building owner must test the actuator per program procedures, and report the results to Invensys' Program Coordination Office on the required forms. Invensys will replace those actuators that fail to properly function during testing.

Manufactured In:
United States
Recall number:
03-502

Note: Individual Commissioners may have statements related to this topic. Please visit www.cpsc.gov/commissioners to search for statements related to this or other topics.

If you are experiencing issues with a recall remedy or believe a company is being non-responsive to your remedy request, please use this form and explain the situation to CPSC.

About the U.S. CPSC

The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. Since the CPSC was established more than 50 years ago, it has worked to ensure the safety of consumer products, which has contributed to a decline in injuries associated with these products.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC. 

For lifesaving information:

Choose Your Recall Emails Get Notified About Each Recall via Email.
Report an unsafe product