LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop installation or after installation could cause the unit or components to fall and injure bystanders.
About 4,200 ventilation units
Affected sales representatives and original equipment manufacturers are being contacted directly. For additional information, contact Greenheck at (800) 931-6579 between 8 a.m. and 5 p.m. CT Monday through Friday, or email Kathy.Lenard@greenheck.com.
Recall Details
Affected units are Sidewall, Rooftop and Centrifugal Inline ventilation units built between August 11, 2004, and April 29, 2005, containing 16 thread-per-inch 3/8-inch by ?-inch spinlock bolts with LUX head markings. Affected model numbers are RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 with serial numbers 04HXXXXX through 05DXXXXX. The model and serial numbers are found on metal identification plate on the units.
LUX spinlock bolts in affected units will be replaced at no cost to the end user.
Greenheck is aware that 309 LUX bolts that have failed in the field. There are no reports of ventilation units falling or any injuries.
If you are experiencing issues with a recall remedy or believe a company is being non-responsive to your remedy request, please use this form and explain the situation to CPSC.
The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. Since the CPSC was established more than 50 years ago, it has worked to ensure the safety of consumer products, which has contributed to a decline in injuries associated with these products.
Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.
For lifesaving information:
- Visit CPSC.gov.
- Sign up to receive our email alerts.
- Follow us on Facebook, Instagram, X, BlueSky, Threads, LinkedIn and Truth Social.
- Report a dangerous product or product-related injury on www.SaferProducts.gov.
- Call CPSC’s Hotline at 800-638-2772 (TTY 800-638-8270).
- Contact a media specialist.