These sprinklers could fail in a fire, exposing the public to bodily injury or death.
Approximately 1 million
Consumers and property owners should determine whether their facilities contain these recalled sprinklers and if so, call the Star Sprinkler Recall Hotline at (800) 866-7807 or access the website at www.star-recall.com to participate in the recall.
Recall Details
WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Mealane Corp. of Philadelphia, Pa., is voluntarily recalling up to 1 million "Star" brand fire sprinklers manufactured from 1961 through 1976. These sprinklers could fail in a fire, exposing the public to bodily injury or death. These sprinklers have been installed nationwide, primarily in nursing homes. They also may be found in hospitals, schools, resorts, stores, office buildings, warehouses and supermarkets.
CPSC reports that 67 percent of the sprinklers that were removed from locations across the country and submitted for testing to independent testing laboratories, such as by Underwriters Laboratories and Factory Mutual Research Corp., failed to activate as they should. CPSC has received one report of a Star sprinkler allegedly not functioning in a bedroom fire in a nursing home.
The Star sprinklers being recalled are dry-type models D-1, RD-1, RE-1, E-1 and ME-1 made from 1961 through 1976. The name "Star" appears on the sprinkler, along with the model number and date of manufacture. With "dry-type" sprinklers, portions of the pipe do not have water in them until the sprinkler activates. The former Star Sprinkler Co., of Philadelphia, Pa., sold its assets and changed its name in June 1976 and became known as Mealane Corp.
The Joint Commission on Accreditation of Healthcare Organizations, an independent, not-for-profit organization that evaluates and accredits hospitals and other long-term-care facilities, is supporting the recall with CPSC.
Consumers and property owners should determine whether their facilities contain these recalled sprinklers and if so, call the Star Sprinkler Recall Hotline at (800) 866-7807 or access the website at www.star-recall.com to participate in the recall. Mealane will provide free replacement sprinkler heads and reimbursement for the labor costs of removing and replacing the old units.
CPSC is continuing its ongoing investigation of fire sprinklers.
Consumers and property owners should determine whether their facilities contain these recalled sprinklers and if so, call the Star Sprinkler Recall Hotline at (800) 866-7807 or access the website at www.star-recall.com to participate in the recall. Mealane will provide free replacement sprinkler heads and reimbursement for the labor costs of removing and replacing the old units.
CPSC reports that 67 percent of the sprinklers that were removed from locations across the country and submitted for testing to independent testing laboratories, such as by Underwriters Laboratories and Factory Mutual Research Corp., failed to activate as they should. CPSC has received one report of a Star sprinkler allegedly not functioning in a bedroom fire in a nursing home.
Note: Individual Commissioners may have statements related to this topic. Please visit www.cpsc.gov/commissioners to search for statements related to this or other topics.
If you are experiencing issues with a recall remedy or believe a company is being non-responsive to your remedy request, please use this form and explain the situation to CPSC.
The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. Since the CPSC was established more than 50 years ago, it has worked to ensure the safety of consumer products, which has contributed to a decline in injuries associated with these products.
Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.
For lifesaving information:
- Visit CPSC.gov.
- Sign up to receive our email alerts.
- Follow us on Facebook, Instagram, X, BlueSky, Threads, LinkedIn and Truth Social.
- Report a dangerous product or product-related injury on www.SaferProducts.gov.
- Call CPSC’s Hotline at 800-638-2772 (TTY 800-638-8270).
- Contact a media specialist.