CPSC and Tyco Fire Products LP Urge Immediate Action on Recalled Fire Sprinklers that Can Fail in a Fire

Release Date: September 24, 2026
  • Recalled “wet” sprinkler, which is installed in piping that is filled with water.
    Recalled “wet” sprinkler, which is installed in piping that is filled with water.
  • Recalled “dry” sprinkler, which is used in areas that may be exposed to very cold temperatures and exposed piping does not contain water.
    Recalled “dry” sprinkler, which is used in areas that may be exposed to very cold temperatures and exposed piping does not contain water.

Washington, D.C. – The U.S. Consumer Product Safety Commission (CPSC) and Tyco Fire Products LP (Tyco Fire) are alerting the public again about serious, potentially fatal fire-safety hazards posed by the failure to replace previously recalled Central Sprinkler fire sprinkler heads that may still be installed in homes, residential facilities, and commercial buildings across the United States.  

The affected sprinklers, manufactured from the mid-1970s to June 2001, were originally recalled in July 2001. The recall was subsequently modified in May 2003 and closed on August 31, 2007, after millions of sprinkler heads were replaced. Minerals, salts, and other contaminants in water can degrade the rubber O-ring seals, which can cause the sprinkler heads to fail to activate during a fire. Despite a multi‑year remediation effort, and National Fire Protection Association standards requiring annual, 5-year, and 20-year inspections, testing, and maintenance of fire suppression systems, a significant number of unremediated recalled sprinklers may remain in service, potentially posing hazards to consumers.   

On July 13, 2025, a fire occurred at an assisted living facility in Fall River, MA. The fire claimed the lives of ten residents and injured dozens more. The facility had not replaced dozens of recalled sprinkler heads, despite identification during a prior fire-safety inspection. The fire underscores the need to remind facilities of the dangers posed by unremediated sprinklers and encourage remediation wherever recalled units are still in use.   

CPSC and Tyco Fire are strongly urging all consumers, businesses, property managers, and governmental entities to take the following steps: 

  • Inspect all building fire sprinklers immediately to determine whether any units are subject to the recall.  
  • Replace all recalled sprinklers using a qualified fire-protection professional. 
  • Review historical maintenance records to confirm whether recalled units were previously identified and removed. 
  • Alert building managers, HOAs, facility administrators, schools, hospitals, nursing homes, and any organization responsible for older structures or vulnerable populations. 

This campaign represents an ongoing commitment by CPSC and Tyco Fire to ensuring fire safety and protecting the public from hazardous recalled products. 

For further information, please visit www.tyco-fire.com/Central-Sprinkler-O-Ring-Notice. 

Release Number
26-800

About the U.S. CPSC
The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. Since the CPSC was established more than 50 years ago, it has worked to ensure the safety of consumer products, which has contributed to a decline in injuries associated with these products. 

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

For lifesaving information:

Media Contact

Please use the below phone number for all media requests.

Phone: (301) 504-7908
Spanish: (301) 504-7800

View CPSC contacts for specific areas of expertise

Report an unsafe product