Skip to main content

CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers

Recall Date:
October 02, 2002

產品召回細節

FOR IMMEDIATE RELEASE
October 2, 2002
Release #03-003
Invensys' Recall Hotline: (877) 481-2372
CPSC Media Contact: Ken Giles, (301) 504-7052

 

WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Invensys Building Systems, of Love Park, Ill., is recalling up to 560,000 Siebe actuators for testing and replacement, if necessary, which could be found in fire and smoke dampers. Actuators hold open fire and smoke dampers in a building's heating, ventilation and air conditioning (HVAC) system. A spring mechanism, integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam, and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing.

These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947. See the associated recall alert for more details on the dampers and companies involved.

Building owners and managers whose buildings have dampers containing Invensys/Siebe actuators should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 7 a.m. and 7 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at

www.regcen.com/MA200.

To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Only actuators that fail testing will be replaced.

请注意:各位委员会委员对相关题目可能会发表声明。请访问www.cpsc.gov/commissioners搜寻这一或其它题目的相关声明。

If you are experiencing issues with a recall remedy or believe a company is being non-responsive to your remedy request, please use this form and explain the situation to CPSC.
About the U.S. CPSC

The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury or death associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. CPSC's work to ensure the safety of consumer products has contributed to a decline in the rate of injuries associated with consumer products over the past 50 years.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

For lifesaving information:
Choose Your Recall Emails Get Notified About Each Recall via Email.
Report an unsafe product