System Sensor Recalls Reflected Beam Smoke Detectors

Name of Product:
System Sensor reflected beam smoke detectors
危险:

When used with certain power supplies, the reflected beam smoke detectors can fail to send a signal to the fire alarm control panel that sounds the alarm and fail to alert occupants of a fire.

补救:
Replace
Recall Date:
一月 28, 2014
单位:
About 610
消费者联系

System Sensor at (800) 736-7672 from 7:30 a.m. through 5 p.m. CT Monday through Friday, or online at www.systemsensor.com and click on Resources, then Product Info Library/Technical Field Bulletins, then Safety Bulletins for more information and a list of acceptable power supplies.

回收的详情

说明:

This recall involves System Sensor's reflected beam smoke detectors with model number BEAM1224S and date codes 2111 through 3053. The YMMW format date codes stand for (2111) 2012-November-1st week of Nov. through (3053) 2013-May-3rd week of May. The detectors are ivory and black and measure 10 inches high by 7? inches wide. The model number and date code are printed on a label on the back of the detector's cover and on the product's packaging. The reflected beam smoke detectors were used primarily in commercial buildings as part of the fire alarm system. Detectors used with acceptable power supplies, as listed on the company website, do not need to be replaced.

补救:

Owners with the affected smoke detectors powered by a power supply that is not on the company's acceptable list available online, should contact System Sensor to receive free replacement smoke detectors.  System Sensor and its distributors are contacting purchasers directly.

事故/伤亡:

None reported

Sold At:
Alarm system, security equipment and electrical equipment contractors and dealers for use in commercial building fire alarm systems from November 2012 through May 2013 for about $800.
Importer:

System Sensor, of St. Charles, Ill.

Manufacturer

System Sensor, of St. Charles, Ill.

产地:
United States
召回数量:
14-713

请注意:各位委员会委员对相关题目可能会发表声明。请访问www.cpsc.gov/commissioners搜寻这一或其它题目的相关声明。

If you are experiencing issues with a recall remedy or believe a company is being non-responsive to your remedy request, please use this form and explain the situation to CPSC.
About the U.S. CPSC

The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury or death associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. CPSC's work to ensure the safety of consumer products has contributed to a decline in the rate of injuries associated with consumer products over the past 50 years.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

For lifesaving information:
Choose Your Recall Emails Get Notified About Each Recall via Email.
Report an unsafe product