Skip to main content

CPSC, Mealane Corp. Announce Recall of Star Fire Sprinklers

Name of Product:
"Star" brand fire sprinklers
Hazard:

These sprinklers could fail in a fire, exposing the public to bodily injury or death.

Remedy:
Replace
Recall Date:
August 04, 1999
Units:

Approximately 1 million

Consumer Contact

Consumers and property owners should determine whether their facilities contain these recalled sprinklers and if so, call the Star Sprinkler Recall Hotline at (800) 866-7807 or access the website at www.star-recall.com to participate in the recall.

Recall Details

Description:

WASHINGTON, D.C. - In cooperation with the U.S. Consumer Product Safety Commission (CPSC), Mealane Corp. of Philadelphia, Pa., is voluntarily recalling up to 1 million "Star" brand fire sprinklers manufactured from 1961 through 1976. These sprinklers could fail in a fire, exposing the public to bodily injury or death. These sprinklers have been installed nationwide, primarily in nursing homes. They also may be found in hospitals, schools, resorts, stores, office buildings, warehouses and supermarkets.

CPSC reports that 67 percent of the sprinklers that were removed from locations across the country and submitted for testing to independent testing laboratories, such as by Underwriters Laboratories and Factory Mutual Research Corp., failed to activate as they should. CPSC has received one report of a Star sprinkler allegedly not functioning in a bedroom fire in a nursing home.

The Star sprinklers being recalled are dry-type models D-1, RD-1, RE-1, E-1 and ME-1 made from 1961 through 1976. The name "Star" appears on the sprinkler, along with the model number and date of manufacture. With "dry-type" sprinklers, portions of the pipe do not have water in them until the sprinkler activates. The former Star Sprinkler Co., of Philadelphia, Pa., sold its assets and changed its name in June 1976 and became known as Mealane Corp.

The Joint Commission on Accreditation of Healthcare Organizations, an independent, not-for-profit organization that evaluates and accredits hospitals and other long-term-care facilities, is supporting the recall with CPSC.

Consumers and property owners should determine whether their facilities contain these recalled sprinklers and if so, call the Star Sprinkler Recall Hotline at (800) 866-7807 or access the website at www.star-recall.com to participate in the recall. Mealane will provide free replacement sprinkler heads and reimbursement for the labor costs of removing and replacing the old units.

CPSC is continuing its ongoing investigation of fire sprinklers.

Remedy:

Consumers and property owners should determine whether their facilities contain these recalled sprinklers and if so, call the Star Sprinkler Recall Hotline at (800) 866-7807 or access the website at www.star-recall.com to participate in the recall. Mealane will provide free replacement sprinkler heads and reimbursement for the labor costs of removing and replacing the old units.

Incidents/Injuries:

CPSC reports that 67 percent of the sprinklers that were removed from locations across the country and submitted for testing to independent testing laboratories, such as by Underwriters Laboratories and Factory Mutual Research Corp., failed to activate as they should. CPSC has received one report of a Star sprinkler allegedly not functioning in a bedroom fire in a nursing home.

Recall number:
99-152

请注意:各位委员会委员对相关题目可能会发表声明。请访问www.cpsc.gov/commissioners搜寻这一或其它题目的相关声明。

If you are experiencing issues with a recall remedy or believe a company is being non-responsive to your remedy request, please use this form and explain the situation to CPSC.
About the U.S. CPSC

The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury or death associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. CPSC's work to ensure the safety of consumer products has contributed to a decline in the rate of injuries associated with consumer products over the past 50 years.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

For lifesaving information:
Choose Your Recall Emails Get Notified About Each Recall via Email.
Report an unsafe product