Skip to main content

CPSC, Goodman Company, L.P. Announce Recall of Amana, Trane, and American Standard Brand Package Terminal Air Conditioners/Heat Pumps

  • No image available
Recall Date:
September 30, 2004

Recall Details

FOR IMMEDIATE RELEASE
September 30, 2004
Release #04-229
Goodman's Hotline: (800) 729-6122
Goodman Media Contact: (713) 861-2500 x439
Trane Media Contact: (732) 980-6048 

 

WASHINGTON, D.C. - The U.S. Consumer Product Safety Commission announces the following recall in voluntary cooperation with the firm below.

Name of product: Package Terminal Air Conditioner/Heat Pump (PTAC)

Units: About 875,000

Manufacturer: Goodman Company, L.P., of Houston, Texas

Hazard: Fire hazard resulting from this chain of events: filter becomes clogged due to lack of maintenance, severely restricting airflow and resulting in elevated internal temperature; this may cause two safety switches to stop working during the product's expected life; if the blower wheel then stops when the product is operated in the heating mode, a fire hazard can develop.

Incidents/Injuries: Goodman received 29 confirmed reports of units overheating, including eight instances where the PTAC ignited and, in some cases, caused minor property damage. No injuries have been reported.

Description: These PTACs are owned mainly by commercial and institutional organizations and are used in the lodging industry, apartments, hospitals, nursing homes and assisted living facilities, schools, and government buildings. A small number of the recalled units are owned by individual homeowners. The PTACs are beige in color and are intended for through-the-wall installation. Goodman manufactured all of the recalled units, which were sold under the Amana, Trane, and American Standard brand names. Goodman and Trane/American Standard are separate, unrelated entities. The recalled PTACs consist of Amana brand units manufactured from January 1996 through March 2003, and Trane and American Standard brand units manufactured from January 1996 through August 2002, that use electric heaters rated at 3.5 kilowatts (kW) or greater.
 

Brand Name Serial and Model Numbers
Amana Serial numbers begin with 96, 97, 98, 99, 00, 01, 02, 0301, 0302, or 0303

Model numbers begin with:
PTH073A35; PTH074A35; PTH093A35; PTH093A50; PTH094A35; PTH094A50; PTH123A35; PTH123A50; PTH124A35; PTH124A50; PTH153A35; PTH153A50; PTH154A35; PTH154A50; PTC073A35; PTC074A35; PTC093A35; PTC093A50; PTC094A35; PTC094A50; PTC123A35; PTC123A50; PTC124A35; PTC124A50; PTC153A35; PTC153A50; PTC154A35; PTC154A50
Trane and American Standard Serial numbers begin with A96, A97, A98, A99, A00, A01, A02

Model numbers begin with:
PTHC0701G; PTHC0702G; PTHC0901G; PTHC0901J; PTHC0902G; PTHC0902J; PTHC1201G; PTHC1201J; PTHC1202G; PTHC1202J; PTHC1501G; PTHC1501J; PTHC1502G; PTHC1502J; PTEC0701G; PTEC0702G; PTEC0901G; PTEC0901J; PTEC0902G; PTEC0902J; PTEC1201G; PTEC1201J; PTEC1202G; PTEC1202J; PTEC1501G; PTEC1501J; PTEC1502G; PTEC1502J


The serial and model numbers are below the operating controls under the front cover assembly. To check the serial and model numbers, remove the front cover by pulling it from the bottom straight out until the clips release, then lifting it up. For some units, it is first necessary to remove two ?" screws (in the filter compartment) that secure the front cover.

Sold to: Amana, Trane, and American Standard representatives sold the PTACs to hotels/motels, hospitals, assisted living facilities, schools, and apartment complexes. Heating, ventilation and air conditioning distributors and resellers sold the units to commercial customers and, in some cases, homeowners. The recalled units were sold throughout the U.S. and parts of Canada between January 1996 and March 2003.

Manufactured in: U.S.A.

Remedy: Free thermal safety limit switch. Commercial and institutional owners will install the replacement switch themselves. Individual homeowners can get a free repair. Contact the Goodman Hotline to receive the free replacement thermal safety switch. Inspect and clean the air conditioner/heat pump filters immediately to remove any imminent hazard. Continue to clean these filters every 30 days in accordance with manufacturer's recommendations which can be found at www.regcen.com/PTAC

Owner Contact: Call the Goodman Hotline at (800) 729-6122 between 7 a.m. and 6 p.m. CT Monday through Friday. Owners can submit a PTAC Recall Information Form at Goodman's Web site www.regcen.com/PTAC

Picture of Recalled Air Conditioners/Heat Pump

Note: Individual Commissioners may have statements related to this topic. Please visit www.cpsc.gov/commissioners to search for statements related to this or other topics.

If you are experiencing issues with a recall remedy or believe a company is being non-responsive to your remedy request, please use this form and explain the situation to CPSC.
About the U.S. CPSC

The U.S. Consumer Product Safety Commission (CPSC) is charged with protecting the public from unreasonable risk of injury or death associated with the use of thousands of types of consumer products. Deaths, injuries, and property damage from consumer product-related incidents cost the nation more than $1 trillion annually. CPSC's work to ensure the safety of consumer products has contributed to a decline in the rate of injuries associated with consumer products over the past 50 years.

Federal law prohibits any person from selling products subject to a Commission ordered recall or a voluntary recall undertaken in consultation with the CPSC.

For lifesaving information:
Choose Your Recall Emails Get Notified About Each Recall via Email.
Report an unsafe product